Specifications – MLC9000+Z1301
| Parameter | Specification |
|---|---|
| Relay Contacts Rating | 2A Resistive 120-240V AC |
| Date of Manufacture | 02/2015 |
| Model | MLC 9000-Z1301 (datasheet) |
| Function | One Universal input, one Heater Break input, two SSR/relay outputs and one Linear output or three SSR/SP relay outputs (datasheet) |
| Process Input Type | Universal (TC, RTD, DC linear V, DC linear mA/mV) (datasheet) |
| Other Inputs | Heater Break (datasheet) |
| Output Type | Relay, SSR, DC linear (datasheet) |
| Max. Number of Outputs | 48 max per system (datasheet) |
| Max. Number of Loops | up to 32 per system (datasheet) |
| Control Type | PID, ON/OFF, Manual, Alarm, Multi-loop, Soft start (datasheet) |
| Scan Time | 100ms (datasheet) |
| Heater Current Input | 0 to 50mA, 0 to 60mA Sinusoidal rms, from Current Transformer. Scaleable 0.1 to 1000AAC (datasheet) |
| Heater Current Input Sampling Method | Delta-sigma at 1kHz (datasheet) |
| Heater Current Input Resolution | 8 bits over 250mseconds rolling window (datasheet) |
| Heater Current Input Accuracy | Better than ±2% of span (datasheet) |
| Heater Current Input Span | 0 – 60mA rms (datasheet) |
| Heater Current Input Range Maximum | Adjustable 0.1A to 1000.0A (datasheet) |
| Heater Current Input Range Minimum | Fixed at 0A (datasheet) |
| Dimensions (Loop Module) | 100mm x 22mm x 120 mm (HxWxD) (datasheet) |
| Mounting | DIN rail mounting via supplied interconnect module (EN50022, DIN46277-3) (datasheet) |
| Ambient Temperature | 0C to 55C (32F to 131F) (datasheet) |
| Storage Temperature | -20C to 80C (-4F to 176F) (datasheet) |
| Relative Humidity | 30% to 90% non condensing (operation and storage) (datasheet) |
| Approvals & Certifications | EMC: Certified to EN61326. Safety: Complies with EN61010 and UL 3121-1 (datasheet) |
| Hot Swapping | Yes, with auto loop configuration (datasheet) |